All guides

What Size Breaker Do I Need?

Find the load in amps, add 25% if it runs for hours, then round up to the next standard breaker. Here is the chart — and the wire-size rule people miss.

Breaker Size Calculator

Enter the load in amps or kW for the standard breaker rating, continuous factor applied.

A breaker exists to protect the wire behind it, not the appliance in front of it. So sizing is a two-step job: find the load’s current, then pick the smallest standard breaker that is above it — while making sure the wire can carry that breaker’s rating. Get either half wrong and you have either nuisance trips or an unprotected cable.

Step 1: find the full-load current

Read it off the nameplate, or work it from the power: amps = watts ÷ volts (divide again by power factor for motors and other inductive loads). A 3,000 W heater on a 240 V circuit draws 3,000 ÷ 240 = 12.5 A. On a 120 V circuit the same 3,000 W would draw 25 A — volts matter.

Step 2: add 25% for continuous loads

A continuous load runs at or near full current for three hours or more — EV chargers, water heaters, storage heaters, big freezers. Breakers heat up under a sustained load, so the rule is to load them to no more than 80%, which is the same as sizing the breaker at 125% of the running current. A 16 A continuous load becomes a 16 × 1.25 = 20 A design current.

Step 3: round up to a standard size

North American (NEC) and international (IEC) ladders differ, but the logic is identical:

NEC (amps)IEC (amps)Typical use
1516Lighting, general receptacles
2020Kitchen, small appliances
3032Dryer, water heater
40 / 5040 / 50Range, EV charger, sub-panel

Breaker Size Calculator

Enter the load in amps or in kW with voltage and power factor — it applies the 125% continuous factor and returns the next standard breaker size.

The rule people miss: the wire must match

The wire’s ampacity must be at least the breaker rating, allowing for installation method, grouping and temperature. This is why 14 AWG (2.5 mm²) pairs with a 15 A breaker and 12 AWG (4 mm²) with a 20 A. Never upsize a breaker beyond what the existing wire can carry to stop nuisance trips — upsize the wire instead, or you remove the cable’s protection.

Why does a breaker trip when a motor starts?

Motor inrush can hit 6–8× the running current for a fraction of a second, tripping a fast breaker even though the running load is fine. Motor circuits use an inverse-time or HACR breaker — a C or D curve in IEC terms — of the same rating that rides through the surge, rather than a bigger breaker that would leave the wire under-protected.

This gets the rating, not the whole design

Breaker choice also involves the interrupting rating (AIC), coordination with upstream devices, and ground-fault or arc-fault protection where the rules require it (GFCI / AFCI). Use this to get the size right, then confirm the full design against the wiring rules that apply to your installation.

ExequtechOS

Do the whole job in one place

A calculation is just the start. ExequtechOS takes it from estimate to quote, job card, invoice and paid — for your whole team.

Get started with ExequtechOS
  • Turn these numbers into a client-ready quote
  • Job cards, invoicing & inventory in one place
  • Works offline in the field, syncs when you’re back