Conduit Fill Calculator
Work out the smallest conduit that fits your conductors — or check a size — using the NEC Chapter 9 fill limits (53% for one wire, 31% for two, 40% for three or more). Pick the conduit type (EMT, rigid, IMC, PVC) and wire insulation, add your conductors, and get the size, fill percentage and a pass/fail. Everything runs on your device.
Guide: How Many Wires Can I Put in a Conduit? (Conduit Fill)Conduit & wire type
Conductors
NEC Chapter 9 fill only
This applies the NEC Chapter 9 fill limits — 53% for one conductor, 31% for two, 40% for three or more — using the Table 4 conduit and Table 5 conductor areas. It does not size the conductors themselves, or apply ampacity derating for more than three current-carrying conductors in a raceway (NEC 310.15) — check that separately with the cable size and voltage drop calculators.
Questions & answers
Everything you need to understand the conduit fill calculator.
How many wires can I put in a conduit?
The NEC limits how full a conduit can be: 53% for a single conductor, 31% for two, and 40% for three or more (Chapter 9, Table 1). Add up the cross-sectional areas of your conductors (Table 5) and compare with that percentage of the conduit’s internal area (Table 4). For example, a ¾″ EMT holds sixteen 12 AWG THHN conductors at the 40% limit. The calculator does the table lookups and the arithmetic.
Why is the fill limit 40%?
The 40% limit for three or more conductors leaves room to pull the wires without damaging the insulation, and lets heat escape. A packed conduit is hard to pull and traps heat, which derates the conductors. The limits tighten for one or two conductors (53% and 31%) because a single or pair of wires jams and heats differently — those are the Chapter 9, Table 1 figures the calculator uses.
Do I count the ground wire in conduit fill?
Yes. Every conductor in the raceway counts toward fill, including the equipment grounding conductor (EGC) and the neutral — even though the ground carries no current in normal operation, it still takes up space. It does not, however, count as a current-carrying conductor for ampacity derating; fill and derating are separate checks.
Does the wire insulation type change the answer?
A lot. THHN/THWN-2 is thin, so more fit; older THW and some XHHW are fatter for the same gauge and fewer fit. Pick the insulation printed on your wire — the calculator switches to that insulation’s Table 5 areas, so the fill and conduit size come out right.
Does this account for derating with many conductors?
No — conduit fill and ampacity derating are two different rules. Once you have more than three current-carrying conductors in a raceway, NEC 310.15 derates their ampacity (for example, 4–6 conductors to 80%), which can force a larger wire — separate from whether they physically fit. Size the wire (and check derating) with the cable size calculator, then use this tool for the conduit.
What about a short nipple between boxes?
A conduit nipple 24 inches or shorter is allowed 60% fill (NEC Chapter 9, Note 4) and the derating factors don’t apply to it. This calculator uses the standard 40/31/53% limits for a normal run; for a true nipple you can fit more, but keep the 60% in mind rather than overstuffing it.
More electrical tools
Cable Size & Wire Gauge Calculator
Minimum cable size and wire gauge for a load and run length.
OpenVoltage Drop Calculator
Volt-drop over a cable run at a given current.
OpenBreaker Size Calculator
The standard breaker rating for a load.
OpenkW to Amps Calculator
Convert power to current — DC, single or three phase.
OpenExequtechOS
Do the whole job in one place
A calculation is just the start. ExequtechOS takes it from estimate to quote, job card, invoice and paid — for your whole team.
Get started with ExequtechOS- Turn these numbers into a client-ready quote
- Job cards, invoicing & inventory in one place
- Works offline in the field, syncs when you’re back